New WA Rules Screw Over Rural Solar, Battery & EV Buyers

2022-08-26 08:42:04 By : Mr. frankie zhang

Ready for some quotes? Enter your postcode now

Earlier this year in Western Australia, a rule went into effect that all new or altered electricity network connections must have a circuit breaker as the main switch.  In some cases, this circuit breaker will trip if you use more than a piddly 20 Amps in your home.

This is not retrospective. Existing homes must only comply with the new rules if they undergo a major electrical alteration such as installing solar, batteries or an electric car charger1.

Replacing the main switch with a circuit breaker results in the enforcement of maximum demand limits for an electrical installation.

In other words, you need to watch how much power (i.e. Amps) you use at any one time, otherwise the main switch may trip, leaving your house without power until you switch stuff off and reset the breaker.

The network service capacity in the Perth metro and major regional areas is different from our cousins in rural Western Australia. Unfortunately, as usual, the country cousins get the worst deal.

The following are network service capacities for Western Power and Horizon Power customers in WA, and therefore the mandated main switch circuit breaker sizes.

For those of you struggling to view the chart on your phone, that’s:

Not for me. I’ve got 63 Amps and no electric car! But it could be a problem if you want to fast charge an EV, if you want your home battery to be part of a VPP, or for any household limited to a maximum of 32 Amps per phase at any one time. That’s not a lot of Amps to play with in the 21st century.

Hubby will be in deep shit if he tries to strike up the arc welder in the back shed and trips the main switch while wifey’s cooking the Sunday roast chicken in the oven2.

Even if your loads are balanced across 3 phases, you’ll have to be careful when using high-powered appliances such as air conditioners, water heaters and ovens.

I’d go as far as saying it’s going to make life more than uncomfortable for rural households on single phase running their air conditioners on a hot summer day while simultaneously trying to get on with their life.

People may even avoid installing solar panels, batteries, air conditioners, induction hobs, electric hot water or car chargers to avoid triggering the requirement on their homes.

Let me be clear. Your solar power system will never overload and trip your new main switch/circuit breaker. In fact, your solar power system will help to reduce your maximum demand by taking the strain off the grid during the daytime. Yay for solar energy!

You: “What about exporting my power?”

Me: “Same thing. Exporting power will not trip your main switch/ circuit breaker by overloading it.”

The largest inverter sizes allowable in Western Australia will only ever export at a maximum rate of about 21A per phase. This will be even less when you’re using power during the day. Yay again for solar!

Clause 4.5.3 in Basic Embedded Generator (EG) Connection Technical Requirements tells us you might need an extra pole in your new main switch/circuit breaker if a Western Power AMI meter is used for DER (distributed energy resources) management purposes.

This will be connected to the auxiliary function terminal of an AMI meter. The auxiliary function terminal may be used for either direct or indirect control of your inverter.

Yes, big brother will have the ability to turn on and off your solar power system – but don’t worry. It’s hopefully almost never going to happen as Finn clearly explains here.

You: “What about when the sun goes down? Won’t I have to watch my usage more carefully or risk my power going out?”

Me: “Oh shit, I forgot about that. Um, would you like to buy a battery?”

Like solar inverters, home battery systems also have size limitations. Electricity network rules in Western Australia ensure that your battery will only ever charge and/or discharge at a maximum rate of about 21 Amps per phase.

Me: “In addition to size limitations, there are also time-of-operation limitation rules.”

You: “You’re f*ing kidding me.”

Nope. Western Power have that covered. See clause 4.3.3 in Basic Embedded Generator (EG) Connection Technical Requirements. The following is mandatory:

10am to 3pm – no discharging. 6pm to 9pm – no charging from the grid.

Good news. The above times are already configured into the battery setup by your installer so you don’t have to worry. But here’s where it gets tricky. The following is recommended but not mandatory:

6am to 10am – avoid charging if battery level is greater than 50% 3pm to 9pm – may discharge for net-load reduction. 9pm to 6am – may charge or discharge as required.

If your battery is configured to charge from the grid, you’ll have to watch your power usage at that time, otherwise you may trip your main switch/ circuit breaker. If your battery is charging at 21 Amps, that only gives a rural WA home 12 Amps (2.8 kW) to play with. A kettle and toaster together will pull more than that.

You: “So I’m damned if I do, damned if I don’t?”

Me: “Not necessarily. You are only likely to be on a 32 Amp breaker with 3-phase power, otherwise you’ll have a generous 63 Amps to play with. Although rural folks only get 32A on single phase.”

If you’re a 3-phase customer and you’re nice to your installer, he will lovingly and professionally balance your loads across all 3 phases and have a nice conversation with you about energy management. This would include configuring your battery to best suit your particular situation.

This battery stuff I told you about above will probably never be an issue… unless… you’re a country cousin living on a rural property with a 32A single phase or 20A split-phase supply. My heart goes out to you brothers and sisters, you are well and truly screwed. A kettle, toaster and bar heater all on at the same time will bring you to the edge of tripping that 32A breaker.

If you’re lucky or rich enough to own an electric car, then read on. If you’re wondering when to make the EV move, you better jump in for the ride too.

With regard to this discussion about the ramifications of the new main switch/circuit breaker rules in Western Australia, it’s best to think of your EV as a battery on wheels. When you plug it in at home, it’s subject to the same rules as a home battery.

Most dedicated single-phase and 3-phase home EV chargers are rated at 32 Amps per phase.

You: “32 Amps, ouch. That’s a pretty fine line as far as my main switch/circuit breaker is concerned. Won’t it trip straight way?”

Me: “No way. The clever people that make EV chargers thought of that. Read on.”

There are smart chargers on the market that can charge at different rates. You can also schedule charging for off-peak times, and in some cases, the charger will automatically switch off other large household loads for you when you’re charging.

For more on this subject, I thoroughly recommend you read Finn’s EV Charging 101 Guide.

Fortunately, Synergy (WA electricity retailer) is using the carrot approach rather than the big stick to tempt you away from peak usage times, and now offers a reduced tariff for off-peak electricity called Midday Saver. Do your sums.

EV charging during off-peak times may save you dollars and go a long way to prevent accidental tripping of your now despised main switch/circuit breaker by reducing the chance other appliances are running while you charge your EV.

Under current rules, you need permission from Western Power to discharge an EV battery into the grid (V2G). You can apply here.

This is Western Power’s official word – New Requirements for WA.

Electricity networks across the world have a colossal job in front of them trying to knock their respective grids into shape to accommodate an evolving decarbonised energy profile.

It’s not as easy as “let’s just put on lots of solar panels and drive around in electric cars”. There are very real engineering and technological challenges to work through, thankfully by people smarter than me.

My guess is that the main switch/circuit breaker ruling is a tool (a very blunt one) to help Western Power manage aspects of the energy profile and power quality by addressing load creep, phase imbalance and flattening the load profile curve.

They are very aware of the imminent wave of power-hungry electric vehicles coming to our shores and want to be prepared.

I’ve already told you our rural neighbours have to make do with a measly 32A single phase or 20A split-phase supply while living in a modern electrified world. This is totally unworkable and really needs to be addressed.

The other thing that irks me is that although this ruling is for all new and altered connections, it mostly affects people installing solar, batteries and EV chargers. These are the very people driving the much-needed energy revolution. They should be rewarded, not penalized!

Double standards? Should this be rolled out across the state for all Western Power customers? Are solar power and battery owners somehow classed as high-energy users above others?

The last thing we want is for people to turn away from solar power, batteries and electric vehicles simply because of an ill-conceived regulation.

On the other hand, is this a good measure to keep everyone’s energy usage in step to help an evolving electricity network?

Me: (in a pirate voice) “Arrr, circuit breakers for everybody or none at all I say! Arrr you with us or against us?”

You: “Reply in the comments section below with or without pirate voice.”

After this article was written, a Western Power spokesperson reached out with the following response to my earlier communication:

“Western Power is aware of concerns raised by the electrical industry on the adequacy of the standard regional and rural supply allocation as customer energy needs change. In response, it is reviewing and assessing the opportunities, risks, and consequences of alternative options, and will provide an update to stakeholders by the end of the year.”

Sign up for our weekly newsletter!

A master in the art of avoiding the rat race. Can be spotted juggling many balls in the air at once. Current and previous exploits include - electrician, solar installer, musician, teacher, blogger and environmentalist.

1) My daughter in South West WA has just moved into her first new home, as a good father I promised to buy her a solar system, if she went gasless in her choice of appliances, hot water etc. Should I wait until this debacle has been sorted? 2) Moving further south next year to Molloy Island, had Plico install a 8.8Kw solar plus 10Kw battery system last month, a Western Power went to change the old meter over yesterday, but couldn’t because it has a single neutral connection, is this part of the changes by Western Power?

That rural limit (16 A/phase for a 480 volt (240 + 240) )system, probably a swer line, is astonishing. We have a rural property on a swer line, our pole fuse is 100Amp on a 240 volt wired transformer. Meter panel main fuse is 80 amp. We did fit an 80 amp circuit breaker for our main switch and have tripped it on several occasions during social functions.

Sounds like you have great parties!

You have got to be kidding. An 80 Amp circuit breaker will not trip until until nearly 120 Amps. A kettle takes 8 Amps. A hot water system usually takes 10Amps. A microwave and toaster may take 4 Amps. What on earth were you running?

Hm-mm, I am of the understanding that here in WA you can only have a 5kW inverter – if you wish to receive a FiT – single or 3 phase. That is, 21A on a single phase, or an average of 7A per phase, on 3 phase (good for less voltage rise, not so good if any one phase goes excessively high shutting down the inverter – an early problem we had, that was fixed by Western Power). Our 3-phase inverter runs from 6.24kW of panel rating – but only clips to 5kW a couple of hours around midday over summer. Trouble free for approaching 6 years (touch wood) – we are finally ‘in the black’.

Interestingly, our incoming power is protected by fuses rated at 100A per fuse!. This will be good if long-range EV prices ever come down to less than drug-money levels!

We experienced this problem in May when ordered to replace wooden pole ?meter box , the contractor tried his up most to speak to and put our case forward . He was stonewalled by some power person in Perth who had no idea about rural properties running welders , wool presses air compressors and a homestead . The power persons take was upgrade your transformer, which is 10 kva and working fine to 25 kva at our cost . All our neighbors have had similar expriences . Frustrated by this stupidity Brian ,great southern farmer.!!!!!!!

Here in Rural NSW I am on a 2 phase 480v supply. The 5 farmlets are on a 25Kw transformer. I used to overvoltage trip my inverters consistently, until the control was changed to voltage control. Now we all have better Solar PV voltage regulation because I wind back when the voltage goes high. I think I actually export more now because my inverters run all the time. (about a 2 min cycle if the inverter trips). I have 12Kw of Zenaji batteries, that get out house through the morning & evening peaks. (I recharge to 30% at 1am for the breakfast rush!) The battery is usually full by 10am. My electric cars are charged by 10a circuits atm. I will be installing a 32A EVSE very soon. btw, EV charger efficiency drops markedly at less than 10A, so the 10A charger should be the slowest you use (at abt 15Km/Hr charge at 10A)

One thing that can be done in WA Rural is to run a virtual off-grid setup. Design the system to run mostly off the Solar PV + Batteries & really try to only use the grid as a virtual generator. There is a Dairy farmer doing just that, that was on the Rural show on Rural ABC radio recently. Dairy farmers must reliably run the refrigeration for the milk. In some cases this uses most of the available power.

In my best pirate voice this seems to signal the approach of the death spiral for the power companies given the rising connection charges as well as restrictive regulations at least as far as early adopters are concerned. If you have a property with spare roof space operating two parallel off grid systems would now seem interesting. We have a mostly electric home with gas space heating and were looking at moving to all electric this now seems less attractive especially as gas prices are now on offer with a 50% discount in WA. I have friends in the US who have no electric power connection and large solar systems and use gas to power back up generators maybe this is food for thought. This avoids the electric power connection fee and one is then free to have a solar system of choice.

Kim Wainwright, “My guess is that the main switch/circuit breaker ruling is a tool (a very blunt one) to help Western Power manage aspects of the energy profile and power quality by addressing load creep, phase imbalance and flattening the load profile curve.”

I’d suggest Australia needs to become much more energy efficient, and homes need to be a contributor to that process.

Per an Energy Source & Distribution article headlined It’ll be impossible to replace fossil fuels with renewables by 2050, unless we cut our energy consumption, dated Aug 25, began with:

Energy consumption—whether its heating your home, driving, oil refining or liquefying natural gas—is responsible for around 82 per cent of Australia’s greenhouse gas emissions, writes Mark Diesendorf, Honorary Associate Professor at UNSW Sydney.

Unless Australia reduces its energy consumption, my recent study finds it’ll be almost impossible for renewable energy to replace fossil fuels by 2050. This is what’s required to reach our net-zero emissions target.

https://esdnews.com.au/itll-be-impossible-to-replace-fossil-fuels-with-renewables-by-2050-unless-we-cut-our-energy-consumption/

Rural customers with a little bit of extra land than their city cousins, are in a great position to install a second Solar PV + Battery Storage Off Grid Solution on their property in addition to an already existing On Grid System.

Importantly the second Off Grid Solution is entitled to STC’s and the System size can be quite large. The CER rule is that the second system plus the first system must in total be no greater than 100 kW. So if you have a 10 kW On Grid System you could install a 90 kW Off Grid Solution for a total of 100 kW of Solar PV Systems and receive the full quota of STC,s applicable to the location, for that 90 kW Off Grid Solution.

The optimum systems inter-operability functionality, including load circuits switching and control between the Grid Supply Source and the Off Grid Supply Source, will require the services of an Off Grid Solutions Integrator specialist experienced in these designs.

The voters of WA elected a government tjhat is owned by the fossil fuel companies..

The state government wants to fprce all households to return to using stoves, heating, and water heating, that burn organic matter, be it wood, coal, or gas.

Well, aren’t i lucky…. horizon power is much better 🤫

Please keep the SolarQuotes blog constructive and useful with these 4 rules:

1. Real names are preferred - you should be happy to put your name to your comments. 2. Put down your weapons. 3. Assume positive intention. 4. If you are in the solar industry - try to get to the truth, not the sale. 5. Please stay on topic.

Notify me of follow-up comments by email.

Notify me of new posts by email.

Read The Good Solar Guide Free Online!

Ready to get quotes for solar?

Get up to 3 FREE quotes through our service

We carefully pre-vet All of

Our installers and your quotes are zero-obligation

Download the first chapter of The Good Solar Guide, authored by SolarQuotes founder Finn Peacock, FREE! You’ll also start receiving the SolarQuotes weekly newsletter, keeping you up to date on all the latest developments on Australia’s solar scene.

We respect your privacy and you can opt out from the newsletter at any time.